To address the low accuracy of faulty feeder detection methods based on single-fault characteristics, we propose a faulty feeder detection method for resonant grounding systems that fuses multiple transient characteristics. First, we analyze the transient zero-sequence current fault characteristics of both faulty and healthy feeders during single-phase-to-ground (SPG) faults. Then, the transient zero-sequence current of each feeder is decomposed into intrinsic mode functions (IMFs) using variational mode decomposition (VMD), and a new signal was constructed by combining IMF1 and IMF2. Subsequently, transient energy and waveform similarity fault characteristics are extracted from the constructed signal, and a faulty feeder detection criterion based on multiple transient characteristics fusion is developed. Finally, extensive simulations and field data verify the proposed faulty feeder detection method. The results demonstrate that the method is robust against fault resistance, fault inception angle, fault location, and noise, achieving high accuracy in faulty feeder detection. This method can be widely applied to detect faulty feeders in resonant grounding systems.
Ma et al. (Tue,) studied this question.