Hydro-wind-solar hybrid power systems have become a mainstream configuration for new-type power systems. However, the high proportion of power-electronics-interfaced generation alters system inertia and damping characteristics, leading to complex high-dimensional frequency dynamics and severe stability challenges. This paper investigates the frequency response mechanism and Hopf bifurcation characteristics of the aggregated frequency response model for hydro-wind-solar hybrid power systems. First, primary frequency response models for hydropower, wind power, and photovoltaic (PV) generation are established under a small-signal analysis framework. On this basis, a tenth-order nonlinear dynamic model of the integrated system is constructed by considering hydraulic nonlinearities, virtual inertia control of wind power, and reserve-based frequency regulation of PV systems. Then, Hopf bifurcation theory is applied to analyze stability and oscillatory instability mechanisms of the high-dimensional system. The bifurcation conditions are derived via high-dimensional Jacobian matrix analysis and Routh-Hurwitz criterion, with supplementary normal form calculation and first Lyapunov coefficient derivation to identify the supercritical/subcritical nature of the bifurcation. Finally, numerical simulations under both small and large disturbances validate the theoretical analysis. The results demonstrate that variations in key control parameters may induce Hopf bifurcation, leading the high-dimensional system from a stable equilibrium to sustained low-frequency oscillations. The findings provide insights and practical guidance for stable operation and parameter tuning of hydro-wind-solar hybrid power systems.