PulseExploreJournal ClubDebatesTrendingResearchersJournals
Instagram
HomeExploreJournal ClubTrending
Synapse
⌘+K
Synapse
November 19, 200235 citations

Transformer derating for harmonic currents: a wideband measurement approach for energized transformers

View Full Paper
AKA.W. KelleySEShannon EdwardsJRJ.P. Rhode

Key Points

Key points are not available for this paper at this time.

Abstract

Power system transformers must often be derated where supplying harmonic currents to nonlinear loads. An existing technique uses measurements performed at DC and the fundamental frequency to extrapolate transformer loss for harmonic frequencies. This paper describes an improved measurement technique which allows direct calculation of transformer loss at harmonic frequencies. The measurement is performed on both energized and deenergized transformers in the loaded and unloaded conditions and is supported by theoretical and numerical analysis. Measurements of several distribution transformers show the limitations of the existing derating technique when compared to the method described in this paper.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Kelley et al. (2002) studied this question.

synapsesocial.com/papers/6a1eb4a2e5c5a32e9d9a7b4ahttps://doi.org/10.1109/ias.1995.530386