Urban integrated energy systems (UIESs) are increasingly exposed to uncertainties arising from wind and photovoltaic variability, load fluctuations, and equipment failures, highlighting the need for refined reserve assessment and coordinated operation. This study develops a unified framework that jointly models renewable and load deviations together with a load-dependent failure probability model, using Monte Carlo sampling and K-means scenario reduction to obtain representative system states. A reserve-capacity-oriented optimisation model is formulated to minimise total operating cost—including thermal generation, energy-storage operation, and reserve cost—while satisfying power balance, reserve adequacy, unit operating limits, and state-of-charge constraints. Application to a UIES comprising a 1000 kW load, 800 kW photovoltaic unit, 100 kW wind turbine, five thermal power units (total capacity 1000 kW), and a 250 kW/370 kWh energy storage system shows that reserve requirements fluctuate between −100 kW (downward) and 500 kW (upward) across different scenarios, with uncertainty-driven reserves dominating and failure-related reserves remaining below 100 kW. The optimisation results indicate coordinated operation between thermal units and storage, with storage absorbing surplus renewable output, supporting peak shaving, and providing most upward and all downward reserves. The total operating costs under typical summer and winter scenarios are 2264.02 CNY and 3122.89 CNY, respectively, confirming the method’s ability to improve reserve estimation accuracy and support economical and reliable UIES operation under uncertainty.