The ip-iq harmonic detection method, which is based on instantaneous reactive power theory, involves cumbersome and complex computations. In addition, the adoption of a low-pass filter (LPF) degrades the dynamic response performance of harmonic detection. To achieve accurate and fast detection of grid harmonic currents for efficient power grid compensation, this paper proposes a total current harmonic detection method using a dual second-order generalized integrator (DSOGI). This method eliminates the calculation steps of the active and reactive components of load current that are required in the conventional ip-iq method. More importantly, it replaces the LPF in the traditional detection scheme with a positive-sequence fundamental component extraction structure based on the DSOGI. Simulations and experimental tests are conducted on the proposed method under balanced grid conditions; the total harmonic distortion (THD) is approximately 2%, and the system stabilizes within 0.04 s. The detection speed and accuracy of the proposed method are superior to those of the traditional ip-iq harmonic detection method, the sinusoidal amplitude integrator (SAI)-based method, and the complex coefficient filter (CCF)-based method.