Experimental study on performance improvement and energy savings of split-type air conditioning system using direct evaporative cooling in hot Iraqi climate

View Full Paper
MAMuhsen M. AlsilbiAAAbdalrazzaq K. AbbasMAMohammed A. Al-Tayyar

Key Points

  • The study aims to evaluate the effectiveness of direct evaporative cooling on the performance and energy efficiency of split-type air conditioning systems in hot climates.
  • Conducted field testing of a 1.5-ton split-type AC under summer conditions in Karbala, Iraq.
  • Utilized a 100 mm cellulose pad for direct evaporative cooling positioned near the outdoor condenser.
  • Compared power consumption and coefficient of performance between modified and conventional air conditioning units.
  • Power consumption reduced by up to 24.56%.
  • Coefficient of performance increased by nearly 37.47%.
  • Economic analysis indicated a payback period of about 3 years for the initial investment.

Abstract

The challenge of electricity consumption is one of the most pressing Global issues today. Air-conditioning systems represent a major part of this consumption, and their impact is even more visible in hot-desert climate. A practical approach to mitigate this problem is to pre-cooled ambient air before it enters the outdoor unit, which not only improves system performance. In this experimental study, a split-type air conditioner of 1.5-ton capacity was tested under the summer conditions of Karbala city, Iraq. Direct evaporative cooling technique was adopted using a 100 mm thick cellulose pad, positioned 55 cm away from the outdoor condenser to allow better air-moisture mixing. Comparative measurements were carried out between the conventional units and the modified one. The results showed a reduction in power consumption by up to 24.56% and an increase in coefficient of performance by nearly 37.47%. From an economic point of view, the analysis revealed that the maximum saving in annual electricity cost was about USD 20.45, while the life-cycle saving ranged between USD 220 and USD 365. The payback-time of the initial investment was estimated around 3 years which indicates a relatively short recovery time. Such findings provide a meaningful signal toward adapting environmentally friendly strategies. Schematic representation of the integration of direct evaporative cooling with a split-type air conditioning system and its impact on performance improvement and energy savings under hot climatic conditions of Iraq. • Direct evaporative pre-cooling applied to 1.5-TR split AC in BWh climate. • Field testing conducted under extreme summer conditions (36–48 °C). • Power consumption reduced by up to 24.56%. • COP improved by up to 37.47%. • Economic analysis shows ∼3-year payback period.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Alsilbi et al. (2026) studied this question.