The high rate of photovoltaic integration poses significant challenges in terms of violations of voltage limits in power grids. Additionally, the operational behavior of PV systems under fault conditions requires thorough investigation in receiving-end grids. This paper analyzes the dynamic coupling characteristics between reactive power and transient voltage in a receiving-end grid with high PV penetration and multiple HVDC infeeds, considering typical AC and DC fault scenarios. Voltage adaptability issues in PV generation systems are also examined. Through an enhanced sensitivity analysis method, the suppression capabilities of transient voltage peaks are quantified in the control parameters of low-voltage ride-through (LVRT) and high-voltage ride-through (HVRT) photovoltaic inverters. On this basis, a hierarchical optimization strategy for PV inverter control parameters is proposed to mitigate post-fault transient voltage peaks and improve the transient voltage response both during and after faults. The feasibility of the proposed method has been verified through simulation on a revised 10-generator 39-bus power system. Following optimization, the transient voltage peak is reduced from 1.263 to 1.098. This validation offers support for the reliable grid connection of the Henan Power Grid. In the events of the N-2 fault at 500 kV and Tian-zhong HVDC monopolar block fault, the post-fault voltage at each node remains below 1.1 p.u. This serves as evidence of a significant enhancement in transient voltage stability within the Henan Power Grid, demonstrating effective improvements in power supply reliability and operational performance.