The planning and design of Extra-High Voltage (EHV) overhead power lines require strict adherence to electromagnetic field exposure limits to ensure public safety. This paper presents a comprehensive analysis of the minimum ground clearance required for standard 400 kV transmission towers to comply with international safety guidelines. A review of legislative frameworks across 37 countries indicates a widespread consensus on limiting values of 5 kV/m for the electric field and 100 μT for magnetic flux density. Using analytical methods, the electric and magnetic fields were calculated for four common tower geometries (Cat, Portal, Danube, and Barrel) under varying ground clearances and phase configurations. The results demonstrate that the magnetic flux density is not a limiting factor, as it remains well below safety thresholds even at standard technical clearances. Conversely, the electric field intensity proves to be the critical design constraint, often requiring clearances significantly higher than those dictated by insulation coordination. The study identifies that optimizing the phase sequence in double-circuit towers can reduce the required ground clearance by up to 28%, offering a cost-effective mitigation strategy. These findings provide power line designers with essential decision-making data for the preliminary design phase, enabling the optimization of tower geometry and phase arrangement without the need for computationally intensive simulations.