Key points are not available for this paper at this time.
In this paper, a scheme of combination of voltage-controlled and current-controlled PWM inverters for parallel operation of a single-phase uninterruptible power supply (UPS) is proposed. The voltage-controlled PWM inverter (VCPI) unit as a master is developed to keep a constant sinusoidal wave output voltage. The current-controlled PWM inverter (CCPI) units are operated as slave controlled to track the distributive current. The power distribution center (PDC) performs the function of distributing the output current of each active unit. In this proposed scheme of parallel operation, each of the units can be designed as nearly independent, and the CCPI units do not need a PLL circuit for synchronization. As a result, the parallel operation of UPS is easy to implement and to expand system capacity. For the purpose of illustration, the system, including three single-phase units which operate in parallel, is analyzed and experimental results are given.>
Building similarity graph...
Analyzing shared references across papers
Loading...
Jiann-Fuh Chen
National Cheng Kung University
Ching‐Lung Chu
Southern Taiwan University of Science and Technology
IEEE Transactions on Power Electronics
National Cheng Kung University
Building similarity graph...
Analyzing shared references across papers
Loading...
Chen et al. (Fri,) studied this question.
synapsesocial.com/papers/6a1ca37e0f544c23831d7ec1 — DOI: https://doi.org/10.1109/63.406842