Key points are not available for this paper at this time.
In a DC distributed power system, the interaction between individually designed power modules/subsystems may cause the instability of the whole system. In a small-signal sense, system level stability is determined by the impedance ratio Z/sub o//Z/sub i/. Here, Z/sub o/ is the output impedance of the source module/subsystem, and Z/sub i/ is the input impedance of the load module/subsystem. As a result, an effective way to prevent system instability is defining impedance specifications for modules/subsystems. This paper briefly summarizes existing works and introduces the authors' contribution in defining impedance specifications. A new forbidden region for impedance ratio Z/sub o//Z/sub i/ on the S-plane is proposed as the system stability margin requirement. Based on this proposed forbidden region, the impedance specifications of individual loads are established. Further, a very practical measurement approach is developed to examine whether or not the system stability margin requirement of the forbidden region is satisfied.
Feng et al. (Fri,) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: