Key points are not available for this paper at this time.
This study proposes a novel high-flux pulsating heat pipe that can lift the major constraint of the conventional pulsating heat pipe (PHP) which is unable to function properly upon anti-gravity operations. The proposed PHP introduces additional unbalance force via uneven tube diameter/geometry in the adiabatic sections to tailor the problem in anti-gravity operation. The design contains a three-dimensional configuration circuitry with compact arrangement tubes on the evaporator and condenser. Through this design, the non-uniform three-dimensional pulsating heat pipe (3D-PHP) manipulates the uneven inner diameters of the adiabatic sections to form uneven vapor/liquid distributions in the adiabatic sections to yield a unitary flow pattern that is able to withstand a much higher input power. The present PHP uses methanol as working fluid, with 38% volumetric filling ratio, and has a high-flux of 22.9 W/cm2 and a low the thermal resistance ratio (Ranti-gravity/Rgravity-assisted) of 1.05 when the input power is 800 W. Both the heat flux and thermal resistance ratio for the proposed design are far better than the existing literature.
Tseng et al. (Sat,) studied this question.