This work proposes a vendor-independent integration method for International Electrotechnical Commission (IEC) 61850 Manufacturing Message Specification (MMS) communication protocol into Programmable Logic Controller (PLC) systems that support an open network communication interface available for the PLC program. IEC 61850 is globally well accepted for electrical substation control, and the protocol MMS is used for integrating the electrical substation bay level into the station level, where the PLC orchestrates the process level of the substation and parallel processes. This method was created because most PLCs lines do not natively support any protocol of IEC 61850, although it often needs to be used for the control of electrical substations. For the development of the prototype presented in this paper, PLCs from the Siemens AG families S7-1500 and S7-410, which support open communication over Transmission Control Protocol/Internet Protocol (TCP/IP) with external systems, were used for validation. Different results regarding network communication and PLC program performance are presented in this paper. The implemented solution presents a meaningful implementation of the MMS application layer into the PLC program and was successfully validated with real industrial, single and redundant PLC systems.