Key points are not available for this paper at this time.
This letter presents a comprehensive fault analysis for a modular multilevel converter high-voltage direct current (MMC-HVDC) system with hybrid half-bridge submodules (HBSMs) and full-bridge SMs (FBSMs) under valve-side single-phase-to-ground (SPG) faults. The analysis shows protection for upper arms is necessary due to the inevitable upper arm overvoltage. It further specifies that the proportion of FBSMs utilized in each arm should be at least 86.6% of the available voltage to safely clear valve-side SPG faults without overvoltage in the lower arms. The accuracy of the theoretical analysis is validated in the positive pole of a bipolar MMC-HVDC system with different ratios of FBSMs modelled in PSCAD/EMTDC.
Building similarity graph...
Analyzing shared references across papers
Loading...
Pingyang Sun
UNSW Sydney
Gen Li
North China Electric Power University
Hongyi Wang
Aalborg University
IEEE Transactions on Power Delivery
UNSW Sydney
Cardiff University
Technical University of Denmark
Building similarity graph...
Analyzing shared references across papers
Loading...
Sun et al. (Wed,) studied this question.
synapsesocial.com/papers/68e5fefbb6db643587593155 — DOI: https://doi.org/10.1109/tpwrd.2024.3429783