PulseExploreJournal ClubDebatesTrendingResearchersJournals
Instagram
HomeExploreJournal ClubTrending
Synapse
⌘+K
Synapse
January 1, 1981IEEE Transactions on Power Apparatus and Systems117 citations

Transformer Models for Transient Studies Based on Field Measurements

View Full Paper
EDErik DickWWWilfred Watson

Key Points

Key points are not available for this paper at this time.

Abstract

A variety of models has been developed to represent transformers in switching surge studies. However, there is a paucity of data on the characteristics of large power transformers to provide parameters for utilization in the models. This paper describes a low power field method of saturating large transformers and plotting the instantaneous magnetization curve. Results on a 25 MVA unit allowed the accuracy of several equivalent circuits to be compared. Minor hysteresis loops were observed to obey simple relationships from which two magnetizing inductance models were developed

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Dick et al. (1981) studied this question.

synapsesocial.com/papers/6a854e2990c4f21ff9d594cahttps://doi.org/10.1109/tpas.1981.316870
Ask AI
Helpful
Bookmark
Share
View Full Paper