September 23, 2025ASME Journal of Engineering for Sustainable Buildings and Cities1 citationsOpen Access

Evaluation of Electrodialysis-Liquid Desiccant and Vacuum-Membrane Dehumidification Systems for High-Efficiency Cooling

View Full Paper
KAK AnanthakrishnanAGAnurag Goyal

Key Points

  • The hybrid electrodialysis–liquid desiccant system can reduce energy requirements by up to 85% compared to conventional systems.
  • Power consumption in the vacuum membrane dehumidification system may decrease by 15-91% under different conditions, outperforming traditional systems.
  • As humidity increases, the performance of the electrodialysis–liquid desiccant system declines, impacting energy savings.
  • These hybrid systems illustrate significant potential to save energy in buildings, but require careful evaluation of operating conditions.

Abstract

Abstract Separate sensible and latent cooling (SSLC) systems are a low-energy, sustainable solution to conventional vapor compression systems (VCS) for space cooling. These systems also eliminate synthetic refrigerants with high global warming potential. In this paper, we analyze two electrically-driven dehumidification systems using a first-principles-based thermodynamic simulation: i) a hybrid electrodialysis–liquid desiccant (ED-LD) system combining LD dehumidification and ED regeneration, and ii) a vacuum membrane dehumidification (VMD) system. In both systems, a dew point evaporative cooler is used for sensible cooling before the final supply of cooled air. We estimate that the hybrid ED-LD system can reduce the energy requirement by up to 85% compared to a state-of-the-art VCS in hot and dry climates. However, as ambient humidity increases, the energy needed to regenerate the LD solution rises drastically, and the performance of the ED-LD system decreases. The VMD system uses water vapor-selective hydrophilic membranes to remove moisture from air. We show that it can reduce the power consumption by 15-91% compared to a VCS in different ambient conditions. A higher ambient wet bulb temperature increases the total power requirement of VMD systems as the solubility of the water vapor in the regenerator increases, creating a higher resistance for removing moisture from the system. Overall, these hybrid systems show promising potential to save energy in buildings, but they must be carefully analyzed to assess the feasible operating conditions and system configurations for maximum energy savings.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Ananthakrishnan et al. (2025) studied this question.

synapsesocial.com/papers/68d4759931b076d99fa6d9cfhttps://doi.org/10.1115/1.4069926
Ask AI
Helpful
Bookmark
Share
View Full Paper

Also Consider

Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context:

  1. 1Performance analysis of a novel heat pump type air conditioner coupled with a liquid dehumidification/humidification cycle2017 · 40 citations
  2. 2Desiccant cooling air conditioning: a review2004 · 476 citations
  3. 3Heat and moisture transfer in application scale parallel-plates enthalpy exchangers with novel membrane materials2008 · 106 citations
  4. 4Influence of the type of anion membrane on solvent flux and back diffusion in electrodialysis of concentrated NaCl solutions2014 · 95 citations
  5. 5Gaseous Diffusion Coefficients1972 · 1,209 citations