February 29, 20240 citations

Implementation of Justified Inspection Zone for Fault Location on Overhead Transmission Lines of 110 kV and Above

View Full Paper
DSD.S. SharyginGFGalina FilatovaAYAndrey Yablokov

Key Points

Key points are not available for this paper at this time.

Abstract

The existing normative and technical documentation of operating organizations does not allow for the reliable organization of the minimal possible inspection zone. The article presents research on the implementation of justified inspection zone for fault location on overhead transmission lines of 110 kV and above. The fault location research was carried out on an imitation model in the Simulink / MATLAB software package. Fault location formulae developed by the authors were used under consideration of multitude factors influencing the measurement using the Monte Carlo method. Only the methodological error of fault location was taken into account in the calculation for the implementation of the inspection zone. The most probable (justified) inspection zone was calculated based on the values of fault locations obtained using the calculation formulae. The generalized Gaussian distribution (GGD) and the functions of mathematical expectation and standard deviation were used to implement the justified inspection zone.