Improved Load Frequency Control Design for Interconnected Power Systems

View Full Paper
TVThanh The VanDTD. TanHMHoai Duong Minh

Key Points

  • The research aims to improve frequency stability in interconnected power systems using an advanced control method.
  • Developed a PID controller based on Improved Grey Wolf Optimizer (IGWO)
  • Tested the controller on interconnected systems with thermal and hydropower plants
  • Conducted simulations under continuous load variations and nonlinear conditions
  • Integrated a generation rate constraint (GRC) block for realistic modeling
  • IGWO-PID controller achieved faster stabilization compared to Particle Swarm Optimization (PSO)
  • Minimized frequency deviations effectively
  • Demonstrated robust performance under varying load conditions

Abstract

Managing frequency stability in modern interconnected power systems is a critical challenge, particularly under continuous load variations and increasing system complexity. In response to these challenges, this study introduces an Improved Grey Wolf Optimizer (IGWO)-based Proportional–Integral–Derivative (PID) controller as a solution for effective Load Frequency Control (LFC). The proposed method is tested on interconnected power systems integrating thermal (reheat and non-reheat) and hydropower plants. The simulations focus on continuous load variation and nonlinearity cases, where the GRC block is added in the model to closely mimic real-world operating conditions. The findings demonstrate that the IGWO-PID controller outperforms by achieving faster stabilization, minimizing frequency deviations, and ensuring robust performance compared to the Particle Swarm Optimization (PSO) algorithm. These results highlight the controller’s adaptability and scalability, offering a reliable approach to maintaining stability and operational efficiency in interconnected power systems.