PulseExploreJournal ClubDebatesTrendingResearchersJournals
Instagram
HomeExploreJournal ClubTrending
Synapse
⌘+K
Synapse
February 24, 20261 citationsOpen Access

Generalized Dynamic Security Region of Grid-Following and Grid-Forming Converter-Based Systems by Basin of Attraction Method

View Full Paper
RMRui MaYCYan ChengSWShibo Wang

Key Points

  • To analyze and quantify transient synchronization in converter-dominated systems within renewable microgrids.
  • Utilized the generalized participation factor method and basin of attraction boundary analysis.
  • Developed fourth-order models for better stability quantification.
  • Defined and estimated two types of dynamic security regions using the BOA method.
  • Validated models through electromagnetic transient simulations.
  • Synchronization controls contribute over 70% to transient dynamics.
  • Power-balance interactions account for about 20% of transient behavior.
  • Proposed framework enables systematic dynamic security region estimations.
  • Novel methods empower grid operators to optimize controllable parameters.

Abstract

With renewable integration and zero-carbon microgrids achieving 100% penetration, converter-dominated systems exhibit millisecond-timescale transient synchronization, which challenges existing physical cognitive methods and cognitive methodology with the synchronous generator (SG). In this paper, in order to quantificationally analyze the transient synchronization, a unified framework has been proposed that combines the generalized participation factor (GPF) method and basin of attraction (BOA) boundary analysis using the manifold approach. According to the GPF and BOA analyses, the fourth-order models are essential for accurate stability quantification, with synchronization controls (PLL, VSG, and droop control) contributing greater than 70% to transient dynamics versus about 20% from power-balance interactions. Further, the dynamic security region (DSR) is redefined by two typologies. Type 1 DSR maps stability in active-power injection space, and Type 2 DSR (generalized DSR) delineates limits in the controllable parameter space. The estimation procedures are proposed for these two types of DSRs by the BOA method. Finally, electromagnetic transient simulations and critical clearing time validation are employed for fidelity verification of models and estimation approaches. To sum up, the proposed novel framework enables systematic DSR estimations for renewable-rich power systems, empowering grid operators to optimize converter-controllable parameters and system operation conditions.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Ma et al. (2026) studied this question.

synapsesocial.com/papers/699d3fb3de8e28729cf64573https://doi.org/10.3390/app16042130
Ask AI
Helpful
Bookmark
Share
View Full Paper