Transient Lightning Response of a New Substation Grounding Method Using General FEM Software

View Full Paper
ASAlhassane SyllaCVC. VolatRJReza Jafari

Key Points

  • To investigate the transient response of a novel grounding system under different lightning current waveforms.
  • Conducted numerical simulations using Comsol Multiphysics 6.2 RF module.
  • Validated frequency and temporal domain analyses with existing grounding systems.
  • Compared simulations of the new grounding system with conventional copper grid systems.
  • The new grounding system showed smaller peak impedance compared to conventional systems, especially in high soil resistivity conditions.
  • Under faster lightning pulses, the peak impedance of the new system was significantly lower than that of the copper grid.

Abstract

This paper presents a numerical investigation studying the response of a new grounding system when submitted to different lightning current waveforms. This grounding system features an electrically conductive concrete (ECON) or geopolymer (ECG) square section with a standard steel rebar as an encased electrode (EE) at the center to potentially replace conventional copper or galvanized steel grounding grids in HV substations. Due to the specificity of this new grounding system called ECON/ECG-EE, we decided to perform different transient simulations using the RF module of the general FEM software Comsol Multiphysics 6.2 version. In the first step, both frequency (FD) and temporal domain (TD) analyses were validated using three grounding systems extracted from the literature. Next, several numerical new grounding system simulations were performed and compared with a conventional HV substation copper grid of the same dimensions equipped with vertical rods. We investigated the influence of several parameters, such as ECON/ECG and soil electrical conductivity, the rise-time in current lightning waveform and the frequency dependency of soil parameters. The numerical results obtained demonstrate that ECON/ECG-EE grounding systems submitted to lightning current pulse present a smaller peak impedance than conventional SGSs equipped with vertical rods, particularly in cases with high soil resistivity. Moreover, it was also demonstrated that with faster lightning current pulse, the ECON/ECG system’s peak impedance becomes significantly lower than those obtained for a copper grid with vertical rods.