February 28, 2026International Journal of Heat and Mass Transfer3 citationsOpen Access

Experimental investigation on inclination effects during condensation heat transfer of R515B inside an inner-grooved tube

View Full Paper
FVFilippo Dalla VecchiaNINima IrannezhadMAMaryam Adwan

Key Points

  • This work investigates how tube inclination affects condensation heat transfer of R515B in inner-grooved tubes.
  • Conducted experiments with R515B in a 7 mm OD inner-grooved tube.
  • Varied inclination angles between -60° and +60° in steps of 30°.
  • Analyzed varying mass flux from 50 to 400 kg/m²·s and vapor quality from 0.06 to 0.93.
  • Maintained constant temperature differences between saturation and wall at selected values.
  • Maximum heat transfer coefficient observed at -30° inclination.
  • Efficiency declines significantly at +60° inclination.
  • Heat transfer performance is influenced by flow regimes and gravity on liquid film dynamics.

Abstract

• Experimental analysis of condensation heat transfer in an inclined inner-grooved tube. • Effect of working conditions and tilting angle on heat transfer coefficient explained. • Marked effect of inclination angle at low mass velocity and low vapor quality. • Heat transfer coefficient showed a maximum value at −30° downward inclination. To address the gap existing in the open current literature regarding the effect of tilting angle during two-phase heat transfer inside inner-grooved tubes, this work investigates condensation heat transfer within a 7 mm OD inner-grooved tube. The refrigerant used is R515B, which is an azeotropic mixture selected for its favorable characteristics and low global warming potential. Experiments were performed at fixed saturation temperature of 30 °C, varying the mass flux in the range 50–400 kg/m²·s and the mean vapor quality from 0.06 to 0.93. The tube inclination relative to a horizontal plane was adjusted between -60° and +60°, in steps of 30°. Due to its significant effect on gravity-controlled condensation, the difference between the saturation and wall temperatures was kept constant throughout the tests, at selected values of 3 K and 6 K. Moreover, every test is accompanied with the corresponding flow pattern recorded with a high-speed camera to facilitate the understanding of the two-phase heat transfer mechanism. Findings revealed a noteworthy impact of inclination angle on the heat transfer coefficient. Overall, the most efficient thermal performance is achieved with a downward tube inclination of -30°, whereas the worst performance is observed with an upward inclination of +60°. These variations in performance are closely linked to variations in flow regimes and how gravity affects the thickness, distribution, and interfacial turbulence of the liquid film.