March 6, 2026IET conference proceedings.0 citations

Converter driven stability screening with ESCR benchmark model

View Full Paper
OJOlli-Pekka JanhunenRKRiku KorhonenPPPauli Partinen

Key Points

  • The aim is to address stability challenges in inverter-based power systems by developing a benchmark model.
  • Developed the ESCR benchmark model for EMT simulations.
  • Evaluated IBR technologies under weak grid conditions.
  • Replicated multiple IBR instances in a meshed network.
  • Integrated model into Fingrid's grid connection process.
  • Model reproduces phenomena from wide area EMT studies.
  • Demonstrated converter driven voltage oscillations and fault ride-through responses.
  • Technologies compliant with VJV2024 show improved stability performance.
  • Supports early validation of technology suitability in grid connections.

Abstract

To address the emerging converter-driven stability challenges in Finland's increasingly inverter-based power system, Fingrid has developed an ESCR benchmark model for EMT simulations. This model enables evaluation of IBR technologies under weak grid conditions without the confidentiality constraints of wide area EMT models. By replicating multiple instances of the same IBR in a meshed network, the ESCR benchmark model captures dynamic interactions and allows tuning to specific ESCR values. Simulation results demonstrate that the benchmark model effectively reproduces phenomena observed in wide area EMT studies, including converter driven voltage oscillations and fault ride-through issues. Technologies optimized for weak grid conditions, particularly those compliant with VJV2024 grid code requirements, show improved stability performance. The benchmark model is integrated into Fingrid's grid connection process at two stages, supporting early validation of technology suitability and later verification of plant-level control stability. While not a full replacement for wide area EMT simulations, the ESCR benchmark model provides a practical approach for assessing IBR performance, contributing to secure and stable integration of renewable energy into the Finnish grid.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Janhunen et al. (2026) studied this question.

synapsesocial.com/papers/69aa6f3c531e4c4a9ff595a6https://doi.org/10.1049/icp.2025.4305
Ask AI
Helpful
Bookmark
Share
View Full Paper

Also Consider

Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context:

  1. 1Performing grid test to validate simulation models and converter-driven stability phenomena2026
  2. 2A High-Fidelity Electromagnetic Transient Model of Inverter-based Resources Integrated to an IEEE-9 Bus System for Benchmarking Studies2024 · 1 citations
  3. 3Estimation of equivalent SCR for offshore wind2026
  4. 4Evaluating Frequency Stability with a Generic Model for IBR Penetration and the Implementation of Grid-Forming Control Strategies2024 · 3 citations
  5. 5Small-signal stability assessment method based on online prediction of the critical short-circuit ratio for grid-forming converters2026 · 1 citations