Investigation of Optimum Insulation Thickness in The Wall With Air-Cavity and The Environmental Analysis

MÖMeral ÖzelSŞSerhat ŞengürCÖCİHAN ÖZEL

Key Points

  • The aim is to evaluate the thermal, economic, and environmental impacts of air-cavity walls with varying insulation thicknesses.
  • Used implicit finite difference procedure for numerical analysis
  • Computed annual transmission loads for insulated and uninsulated walls
  • Analyzed energy efficiency during summer and winter seasons
  • Conducted cost analysis to determine optimal insulation thickness
  • Annual cooling and heating loads decreased by about 31% with a 2.5 cm air-cavity
  • Optimal insulation thicknesses identified: 12.4 cm (south), 13.2 cm (north), 13.4 cm (east/west)
  • Annual energy consumption reductions: 87.3%, fuel consumption 87.9%, and emissions 88% with optimal insulation

Abstract

Making energy efficient designs in building walls can be a solution to reduce increasing building energy consumption and thus environmental pollution. By using insulation and energy efficient building materials, the heating and cooling loads of buildings and therefore fuel consumption and environmental pollution can be significantly reduced. Therefore, this paper goals to evaluate the thermal, economic and environmental effects of walls with air-cavities by considering different wall orientations. The study uses a numerical method called the implicit finite difference procedure to compute annual transmission loads for walls that have and haven't air-cavities during the summer and winter seasons in Elazığ province of Turkey. The conclusions show that the annual cooling and heating loads decline by about 31% for all wall orientations when a 2.5 cm air-cavity is positioned in the center of an uninsulated concrete wall. The study also shows that the effect of the air-cavity on heat transmission loads declines as insulation thickness rises. Additionally, walls incorporating air cavities were analyzed to determine their annual average time lag and decrement factor. To identify the optimal insulation thickness, a cost analysis was conducted using annual transmission loads calculated under dynamic thermal conditions. The findings indicate that the most effective insulation thicknesses for walls with air cavities are 12.4 cm for south-facing orientations, 13.2 cm for north-facing, and 13.4 cm for east- and west-facing orientations. When these optimal values are applied across all orientations, the annual heating energy, fuel consumption, and associated emissions are reduced by 87.3%, 87.9%, and 88.0%, respectively.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Özel et al. (2026) studied this question.

synapsesocial.com/papers/69c4ccbbfdc3bde448918284https://doi.org/10.17798/bitlisfen.1795736
Ask AI
Helpful
Bookmark
Share
View Full Paper

Also Consider

Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context:

  1. 1Comprehensive Cost–Energy Evaluation of Wall Insulation for Diverse Orientations and Seasonal Usages2024 · 4 citations
  2. 2Optimising of thermal insulation thickness based on wall orientations and solar radiation using heating-degree hour method2024 · 5 citations
  3. 3The Effect Of The Residential Building’s Wall Thickness and Material On The Heating And Cooling Loads With Special Reference To Using The Green Facades2024
  4. 4Assessment of Insulation Thickness and Window Thermal Transmittance Effects on Peak Heating and Cooling Loads in Residential Buildings2026
  5. 5A methodology to evaluate the optimal insulation thickness for heating and cooling needs in different climatic zones for buildings made of reinforced concrete with cavity walls2024 · 5 citations