May 9, 2026International Journal of Thermal Sciences2 citationsOpen Access

Thermal regulation mechanism of embedded heat-pipe-assisted conductors under high heat-flux electrical loading

View Full Paper
XZXiaogang ZhengRXRichang XianJGJunhao Guo

Key Points

  • The research aims to investigate a passive heat dissipation method for medium-voltage switchgear busbars using heat pipe technology.
  • Developed a multiphysics coupled model to analyze thermal characteristics
  • Used simulations based on specific parameters: load currents up to 1300 A, contact resistances, and busbar lengths
  • Evaluated the effects of an embedded heat pipe on hotspot temperature reduction and operational stability
  • Embedding a 5mm diameter heat pipe at 500 A reduces hotspot temperature by 1.9 K, increasing to 2.4 K at 600 mm length
  • At 1300 A, the effectiveness increases to a reduction of 13 K with 40 μΩ contact resistance achieving a 9.8 K drop
  • The introduced heat pipe extends temperature rise delay time by 385 s and increases expected busbar lifetime under high temperatures by 77%

Abstract

To address the local overheating in the busbar contact region of medium-voltage switchgear caused by high heat flux density, a passive heat dissipation scheme using an embedded heat-pipe-assisted conductor is proposed. An electromagnetic-thermal-fluid-phase-change multiphysics coupled model is established to clarify the influence of heat pipe structural parameters and operating conditions on the temperature rise characteristics of the busbar. The simulation employs a copper–water heat pipe with a 100-mesh sintered copper wire mesh wick and a working fluid filling ratio of 100%. Under conditions of a load current of 500 A, a contact resistance of 10 μΩ, and a busbar length of 300 mm, embedding a heat pipe with a diameter of 5 mm reduces the hotspot temperature of the busbar by 1.9 K; when the busbar length increases to 600 mm, the temperature reduction increases to 2.4 K. When the load current increases to 1300 A, the temperature suppression effect of the heat pipe is significantly enhanced, and the hotspot temperature decreases by 13 K; when the contact resistance increases to 40 μΩ, a temperature reduction of 9.8 K is still achieved. The results indicate that the phase-change heat transfer intensity increases adaptively with increasing thermal load, and the system operating point remains far from the capillary limit, with a safety margin of 2.86. Transient characteristics show that the introduction of the heat pipe extends the temperature rise delay time of the busbar under load step by 385 s. Based on the Arrhenius equation, the proposed scheme can extend the expected lifetime of the busbar under high-temperature conditions by approximately 77%. The embedded heat pipe establishes an axial latent heat transport channel, effectively overcoming the axial heat conduction bottleneck in long conductors and significantly improving the thermal reliability and long-term operational stability of the busbar without altering the external profile.