May 1, 1980IEEE Transactions on Power Apparatus and Systems212 citations

Experience with HVDC - Turbine-Generator Torsional Interaction at Square Butte

View Full Paper
MBM. BahrmanELE.V. LarsenRPR.J. Piwko

Key Points

Key points are not available for this paper at this time.

Abstract

Tests on the the modern HVDC system at Square Butte conducted in October 1977 indicated that the HVDC terminal was interacting in an adverse way with an 11.5-Hz torsional mode of an adjacent turbine- generator unit. Subsequent analytical work duplicated the field test observations and was used to develop an understanding of the HVDC-torsional interaction phenomena. As a result of the analytical work, the control system of the HVDC terminal was modified and subsequent tests showed that the changes resulted in stable operation. The paper includes significant field test and analytical results.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Bahrman et al. (1980) studied this question.

synapsesocial.com/papers/6a154faa814bf8ec9a4e6465https://doi.org/10.1109/tpas.1980.319726
Ask AI
Helpful
Bookmark
Share
View Full Paper

Also Consider

Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context:

  1. 1Small-signal modulation of the Pacific HVDC intertie1976 · 89 citations
  2. 2A Refined HVDC Control System1970 · 69 citations
  3. 3Direct Current Transmission1971 · 783 citations
  4. 4The Navajo SMF Type Subsynchronous Resonance Relay1978 · 28 citations
  5. 5The Phase-Locked Oscillator - A New Control System for Controlled Static Convertors1968 · 146 citations