May 27, 2026Symmetry0 citationsOpen Access

Symmetry-Guided Distributed Control Strategy for Source–Load Coordination in Active Distribution Networks with Electric Heating Loads

View Full Paper
SLShoudong LiLanzhou Jiaotong UniversityJSJinhang SongMinistry of Ecology and EnvironmentGBGuangqing BaoSouthwest Petroleum University

Key Points

  • This study aims to enhance the frequency regulation of power grids through coordinated control of electric heating loads and distributed generators.
  • Developed a thermodynamic dynamic model for electric heating loads
  • Established a source-load coordinated response control framework
  • Designed an improved consensus-based distributed control algorithm
  • Improved convergence speed by 27.5%
  • Maintained steady-state frequency above 49.95 Hz under interferences
  • Significantly enhanced stability and frequency support capability of active distribution networks

Abstract

As a clean heating solution, electric heating loads (EHLs) have become a critical flexible load resource on the demand side in recent years. To enhance the power grid’s frequency regulation capability and mitigate the impacts of both EHLs and high-penetration renewable energy on the power grid, a symmetry-guided distributed control strategy for active distribution networks (ADNs) considering demand response (DR) of EHLs is proposed from the perspective of source–load bilateral coordination. Based on the symmetry of information interaction and control structure between distributed generators (DGs) and EHLs, a thermodynamic dynamic model of EHLs and a source–load coordinated response control framework are established. An improved consensus-based distributed control algorithm and a temperature queue sorting-based distributed response strategy are designed to maintain symmetrical power allocation and symmetrical response coordination between DGs and EHLs, achieving rapid and stable source–load coordination. Finally, comprehensive simulations verify the effectiveness of the proposed strategy. The results show that the proposed strategy improved the convergence speed by 27.5%, achieved fast and effective control of DGs and EHLs, maintained the steady-state frequency above 49.95 Hz under various interferences, effectively eliminated frequency deviation caused by source–load interference, and significantly improved the stability and frequency support capability of ADNs.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Li et al. (2026) studied this question.

synapsesocial.com/papers/6a168ae40c924ddd1bd59af2https://doi.org/10.3390/sym18050866
Ask AI
Helpful
Bookmark
Share
View Full Paper

Also Consider

Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context:

  1. 1Smart Grids: A Cyber–Physical Systems Perspective2016 · 722 citations
  2. 2Two-Stage Load Shedding for Secondary Control in Hierarchical Operation of Islanded Microgrids2018 · 86 citations
  3. 3A control strategy for air-conditioning loads participating in frequency regulation based on model predictive control2024 · 22 citations
  4. 4Optimal Energy Storage Allocation for Mitigating the Unbalance in Active Distribution Network via Uncertainty Quantification2020 · 68 citations
  5. 5Hierarchical collaborative expansion planning for transmission and distribution networks considering transmission cost allocation2021 · 28 citations