June 3, 2026Fire0 citationsOpen Access

Study on Liquid Hydrogen Leakage Dispersion Behavior and Synergistic Mitigation by Barrier Walls and Air Curtains in a Hydrogen Production and Refueling Station

View Full Paper
XLXingyu LiuBYBo YuanSZShiyan Zeng

Key Points

  • This research aims to investigate the effectiveness of barrier walls and air curtains in reducing liquid hydrogen dispersion during leakage incidents.
  • Examined LH2 leakage dispersion in an integrated hydrogen production and refueling station (IHPRS).
  • Compared various barrier wall and air curtain configurations to identify optimal designs.
  • Evaluated dispersion distances under different conditions, including wind speed and leakage flow rates.
  • The optimal structure reduced downwind dispersion distance by up to 58.02% under natural wind conditions.
  • Horizontal dispersion was suppressed by 42.18% in the X-direction and 33.17% in the Z-direction at a flash evaporation mass fraction of 20%.
  • The X-direction dispersion distance decreased by 33.88% with a 40.14% increase in cloud height at a leakage rate of 5.15 kg/s.

Abstract

Compared with gaseous hydrogen at ambient temperature, liquid hydrogen (LH2) possesses a higher volumetric energy density and is therefore regarded as one of the most economically viable hydrogen storage and transportation options. However, the extremely large temperature difference between the storage temperature of LH2 and the ambient environment may give rise to serious safety hazards once a leakage accident occurs. Focusing on an integrated hydrogen production and refueling station (IHPRS), this study investigates the suppression effect of a novel synergistic protection system—combining a barrier wall and an air curtain—on LH2 leakage and dispersion. By comparing the dispersion distances of hydrogen clouds under different barrier wall–air curtain configurations, the optimal synergistic structure was identified as a barrier wall with a planar size of 36 m × 12 m and a height of 3 m, combined with an air curtain velocity of 40 m/s. The reliability of this structure is further evaluated under practical influencing factors: under varying natural wind conditions, the maximum downwind dispersion distance is reduced by up to 58.02%; at a flash evaporation mass fraction of 20%, horizontal dispersion is suppressed by 42.18% and 33.17% in the X- and Z-directions, respectively; and at a leakage mass flow rate of 5.15 kg/s, the X-direction dispersion distance is reduced by 33.88% with a 40.14% increase in cloud height. The results show that the proposed barrier wall–air curtain synergistic protection structure can effectively alter the dispersion path of the FHC (refers to the hydrogen cloud with a volume concentration within the flammable range between 4 and 75% vol) formed by LH2 leakage, shorten the hazardous downwind distance, and enhance the vertical dispersion of the FHC. These findings provide theoretical support and safety guidance for the risk control of LH2 leakage accidents in IHPRS.