Premature Failure of Galvanized Fire Sprinkler Pipes in Coastal Conditions: Evidence of Sequential Atmospheric and Aqueous Corrosion

View Full Paper
OGOz GolanAPAvraham PasternakIKIlana Kolodkin‐Gal

Key Points

  • This study examines the causes behind rapid failures of galvanized fire sprinkler pipes in coastal environments.
  • Forensic analysis using metallography, SEM, and EDS
  • Investigation of corrosion mechanisms due to marine aerosols and stagnant water
  • Analysis of bacterial influence on pipe degradation
  • Pitting initiated by chloride exposure and zinc coating depletion
  • Localized corrosion accelerated by stagnant water and oxygen gradients
  • Presence of sulfate-reducing bacteria led to microbiologically influenced corrosion

Abstract

This case study investigates the rapid through-wall perforation of newly installed hot-dip galvanized (HDG) fire sprinkler pipes in a coastal Mediterranean environment. Failure occurred along the internal waterline of horizontal sections within a short service period. Forensic analysis—comprising metallography, SEM, and EDS—identified a synergistic atmospheric–aqueous corrosion mechanism. Marine aerosol exposure during pre-service storage led to significant chloride enrichment and localized depletion of the 40–50 μm zinc coating, initiating early-stage pitting. Upon commissioning, stagnant water established oxygen concentration gradients and differential-aeration cells, driving localized anodic dissolution. Additionally, sulfate-reducing bacteria (SRB) contributed to accelerated degradation through microbiologically influenced corrosion (MIC), as suggested by sulfur-bearing tubercles. The findings demonstrate that standard galvanizing thickness alone does not ensure longevity in high-salinity environments if atmospheric “preconditioning” occurs. These results underscore the necessity of shielding internal pipe surfaces during storage and construction to prevent premature failure. This case study informs predictive maintenance and material selection for stagnant-water systems in coastal regions.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Golan et al. (2026) studied this question.

synapsesocial.com/papers/6a2115d7d499ed480b16edbfhttps://doi.org/10.3390/ma19112360
Ask AI
Helpful
Bookmark
Share
View Full Paper

Also Consider

Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context:

  1. 1Localized corrosion attack on the galvanised steel pipes of the fire protection system2024
  2. 2Mechanistic Investigation of the Corrosion Behavior of Organic Zn14Al1.4 Composite Coating Under Simulated Tropical Marine Atmospheric Conditions2025
  3. 3Effect of marine atmosphere severity on degradation morphology and barrier integrity of galvanized coatings2026
  4. 4Grooving Corrosion and Premature Leakage Characteristics of Electric-Resistance-Welded Components of Secondary-Side Fire Protection Piping of Pre-Action Sprinkler Systems2026
  5. 5Applied stress on corrosion behavior of hot-dip galvanized steel in NaCl-NaHSO3 solutions2026