March 23, 2016IEEE Transactions on Power Delivery291 citationsOpen Access

Fault Detection and Faulted Line Identification in Active Distribution Networks Using Synchrophasors-Based Real-Time State Estimation

MPMarco PignatiLZLorenzo ZanniPRPaolo Romano

Key Points

Key points are not available for this paper at this time.

Abstract

We intend to prove that phasor-measurement-unit (PMU)-based state estimation processes for active distribution networks exhibit unique time determinism and a refresh rate that makes them suitable to satisfy the time-critical requirements of protections as well as the accuracy requirements dictated by faulted line identification. In this respect, we propose a real-time fault detection and faulted line identification functionality obtained by computing parallel synchrophasor-based state estimators. Each state estimator is characterized by a different and augmented topology in order to include a floating fault bus. The selection of the state estimator providing the correct solution is performed by a metric that computes the sum of the weighted measurement residuals. The proposed process scheme is validated by means of a real-time simulation platform where an existing active distribution network is simulated together with a PMU-based monitoring system. The proposed process is shown to be suitable for active and passive networks, with solid-earthed and unearthed neutral, for low- and high-impedance faults of any kind (symmetric and asymmetric) occurring at different locations.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Pignati et al. (2016) studied this question.

synapsesocial.com/papers/6a6fbe7e2163a0a01bc40344https://doi.org/10.1109/tpwrd.2016.2545923
Ask AI
Helpful
Bookmark
Share
View Full Paper