July 1, 1988IEEE Transactions on Power Electronics136 citations

A high-power multitransistor-inverter uninterruptable power supply system

View Full Paper
JHJ. HoltzWLW. LotzkatKWKarl-Heinz Werner

Key Points

Key points are not available for this paper at this time.

Abstract

The active and reactive load distribution between n paralleled single-phase uninterruptible power supply (UPS) inverters is equalized by virtue of n-1 load-sharing control loops. The approach permits the construction of UPS systems of any desired power rating at maximum utilization of the power components. The method of harmonic cancellation decreases the switching frequency of the power devices while maintaining good dynamic performance. The design details of a 45 kVA UPS inverter system with 150% steady-state overload capability are presented. The performance under various operating conditions is illustrated by oscillograms.>

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Holtz et al. (1988) studied this question.

synapsesocial.com/papers/6a77cc7a6c53f758bc1ea943https://doi.org/10.1109/63.17945