DC distribution systems are increasingly utilized in data centers, electric vehicle charging infrastructures, and microgrids due to their superior power conversion efficiency compared to AC systems. In DC networks, the protection coordination of overcurrent relays (OCRs) is essential for selectively isolating faults and maintaining operational stability. However, the integration of distributed energy resources (DERs), such as photovoltaics, introduces significant challenges by altering the magnitude and rate of change of fault currents. This study conducts a comprehensive analysis of various scenarios by varying both the fault location and the points of common coupling (PCC) for DER. The simulation results reveal that specific configurations lead to critical instances of protection mis-operation and failure to operate, which cause coordination failures and compromised coordination time intervals (CTIs). These findings demonstrate that conventional protection strategies may fail to ensure reliability in DER-integrated DC systems due to the dynamic nature of fault current characteristics. In this paper, these diverse scenarios and the resulting vulnerabilities in protection coordination were modeled and verified using PSCAD/EMTDC V5.0.
Choi et al. (Fri,) studied this question.