Loss of synchronization between wind farm and power grid during severe grid faults would cause wind farm tripping. In this paper, the mechanism of grid-synchronization is uncovered, described as motion of an autonomous nonlinear differential equation with specific initial states. The revealed mechanism indicates that even though steady-state working point exists, improper initial states and poor system dynamic properties could lead to synchronization instability. In order to keep wind farm synchronous with the power grid during severe grid faults, special requirements on system dynamic properties are stated. Moreover, to satisfy all the requirements, a current injecting method is proposed. By adjusting active and reactive output currents of the wind farm, the proposed method could ensure system synchronization stability during severe grid faults. Implementation of the proposed method on PMSG- and DFIG-based wind farm is illustrated. Simulation results validate the analysis and the control method.