Steel tape armored multicore cables are critical components in the transmission and distribution of power in medium- and low-voltage networks. It is difficult to measure current in the individual conductors of multicore cables because they are enclosed within multilayer protective structures (e.g., armor). The magnetic field–current inversion method provides a noncontact alternative for measuring conductor currents, derived from externally measured magnetic fields. However, the nonlinear magnetization effects of the steel tape armor disrupt the linear relationship between the magnetic field and currents, making accurate measurements challenging. To address this issue, we propose a noncontact current measurement method that incorporates the nonlinear effects of the armor layer. This method involves pre-calibrating the coefficient matrices, determining the angle formed between the magnetic sensor array and the multicore cable, and applying nonlinear fitting. This achieves a current measurement accuracy less than 5% and 5° in relative error and phase error, respectively. The proposed method avoids computationally intensive inverse operations, thereby enabling the realization of lightweight, low-cost current measurement terminals for practical field applications.
Wang et al. (Tue,) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: