Poor indoor air quality (IAQ) in naturally ventilated school buildings remains a widespread problem, particularly during the heating season, when limited ventilation leads to elevated CO2 concentrations. At the same time, increasing ventilation rates may significantly increase energy demand, creating a conflict between IAQ and energy efficiency. This study aims to evaluate whether CO2-based demand-controlled mechanical ventilation, particularly with heat recovery (HRV), can improve IAQ while maintaining acceptable energy performance in existing school buildings. A previously validated CONTAM model of a Polish primary school classroom was used to simulate natural ventilation, mechanical exhaust ventilation, and balanced ventilation with heat recovery. In mechanical systems, CO2-based demand-controlled ventilation (DCV) was applied. The resulting airflow rates were then used in EnergyPlus simulations to assess seasonal heating and primary energy demand under Kraków climatic conditions. Increasing the outdoor air supply rate significantly reduced indoor CO2 concentration but led to higher heating demand in exhaust ventilation systems. In contrast, HRV reduced heating energy demand by more than 80% compared with exhaust ventilation while maintaining comparable indoor air quality. Although HRV required additional electricity for fan operation, the total primary energy consumption remained low. The results demonstrate that CO2-based DCV systems with heat recovery provide an effective balance between indoor air quality and energy performance. These findings support the application of HRV as a practical retrofit solution for improving ventilation in existing school buildings.