Key points are not available for this paper at this time.
This paper presents harmonic and reactive power compensation based on a generalized theory of instantaneous reactive power for three-phase power systems. This new theory gives a generalized definition of instantaneous reactive power, which is valid for sinusoidal or nonsinusoidal and balanced or unbalanced three-phase power systems with or without zero-sequence currents and/or voltages. The properties and physical meanings of the newly defined instantaneous reactive power are discussed in detail. A harmonic and reactive power compensator based on the new theory for a three-phase harmonic-distorted power system with zero-sequence components in the load current and/or source voltage is then used as an example to show harmonic and reactive power measurement and compensation using the new theory. Simulation and experimental results are presented.
Peng et al. (Sun,) studied this question.