This article proposes a DC-line protection method improving reliability against high-resistance faults in VSC-HVDC grids, indicating promising results.
High-resistance faults on the DC lines of multi-terminal VSC-HVDC grids lead to insufficient protection reliability, and the introduction of current-limiting strategies alters the system’s intrinsic fault characteristics, degrading protection performance. To address these issues, we propose a DC-line protection scheme that is immune to converter control strategies and highly tolerant to fault resistance. First, based on the grid topology, post-fault current paths are analyzed, and the fault characteristics produced solely by the fault-induced voltage source are identified. A sequential overlapping derivative transformation is then employed to magnify the discrepancy between internal and external faults, forming the core of the fault-identification criterion; the zero-mode component is used for pole selection. Finally, a four-terminal VSC-HVDC model is built in PSCAD/EMTDC version 4.6.2 for validation. Simulation results show that, after applying the current-limiting strategy, the characteristic quantity changes only marginally, and the proposed protection can reliably withstand fault resistances of up to 700 Ω.
No takes yet. Share an insight, caveat, or question.
Zhang et al. (2025) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: