To meet the demands of deep grid integration of renewable energy and long-distance power transmission, this paper presents a hybrid multi-infeed DC system architecture that includes an AC power source (AC), a voltage source converter (VSC), and a modular multilevel converter (MMC). Addressing the limitations of traditional differential protection—such as insufficient sensitivity under high-resistance grounding and susceptibility to false operations under out-of-zone disturbances—this paper introduces an enhanced current differential criterion based on dynamic phasor analysis. By effectively decoupling DC bias and load current components and optimizing the calculation of action and braking quantities, the proposed method enables the rapid and accurate identification of typical faults, including high-resistance grounding, three-phase short circuits, and out-of-zone faults. A multi-scenario simulation platform is built using MATLAB to thoroughly validate the improved criterion. Simulation results demonstrate that the proposed method offers excellent sensitivity, selectivity, and resistance to false operations in multi-infeed complex systems. It achieves fast fault detection (~2.0 ms), strong sensitivity to high-resistance internal faults, and low false tripping under a variety of test scenarios, providing robust support for next-generation DC protection systems.
Liao et al. (Mon,) studied this question.