Answers are grounded in this paper and cite their sources.
The design of legacy-line protection elements has been guided by the behavior of synchronous machines during faults. Because of the significant field-winding inductance and rotating mass, the magnitude, angular frequency, and phase angle of the back-electromotive force (EMF) voltage waveforms of synchronous machines remain practically constant for several hundreds of milliseconds after a fault occurs. This has facilitated the engineering of the memory-polarization technique in mho distance elements, which has been effective for machine-dominant power grids. However, this assumption is no longer held for inverter-based resources (IBRs) because of the lack of field winding and moment of inertia in power electronics devices. Notably, the negative-sequence directional overcurrent protection and the quadrilateral distance elements have been impacted by early IBRs with grid-following (GFL) controls because they did not inject negative-sequence currents during asymmetrical faults.
No takes yet. Share an insight, caveat, or question.
Peralta et al. (2024) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: