Answers are grounded in this paper and cite their sources.
Wind and solar energy inverter-based resources (IBRs) has been employed extensively with the aim of carbon neutrality. Power systems also make extensive use of power electronic converters, leading to interactions between IBRs and with the grid, causing high frequency oscillation (HFO) problems. It damages equipment and jeopardizes the security of the system. To identify HFO components above 100 Hz, this research use Phasor Measurement Unit (PMU) instantaneous value data to determine the HFO associated characteristics. To reduce the influence of spectral leakage and the fence effect, as well as to improve the identification accuracy of the related parameters, this paper adopts the RV self-convolutional window based Discrete Fourier Transform (DFT) and the Hanning double-window based all-phase Fast Fourier Transform (apFFT) hybrid algorithm to identify the HFO modal parameters. We take into account the identification accuracy in complex cases, such as non-nominal frequencies, with noise effects and multiple HFO modes. The simulation results show that the proposed method has high identification bandwidth, accuracy and strong flexibility.
No takes yet. Share an insight, caveat, or question.
Sun et al. (2024) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: