The wind-turbine step-up transformers are subjected to high-frequency high dV/dt transient voltages due to the operation of power electronic converters and vacuum circuit breakers. These high-frequency transients are harmful to the transformer turn-to-turn and layer-to-layer paper-oil insulation. The current research work addresses the effect of the transient voltage parameters on the degradation of the transformer paper-oil insulation. Two-level, two-factor design of experiments were used to obtain the effect of transient voltage parameters on the ageing of the paper-oil insulation. Rise time and switching frequency were the two factors (parameters) selected for the ageing experiments. The two values of rise time were 220 ns and 650 ns, and two values of the switching frequency were 1 kHz and 3 kHz. The faster rise time (220 ns) and higher switching frequency (3 kHz) of the voltage led to a higher degradation for the paper-oil insulation. Additionally, the transient voltage ageing of paper-oil insulation is investigated and compared for two types of mineral oils: Luminol™ TRi oil and Voltesso TM 35 oil, that have differences in their electrical and chemical properties.
No takes yet. Share an insight, caveat, or question.
Devadiga et al. (2024) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: