This analysis investigates cavitation and hydraulic performance in centrifugal fire pumps, revealing critical instabilities.
Centrifugal fire pumps are critical for firefighting systems but suffer from cavitation and instability under off-design conditions. However, systematic analyses of their flow-rate-dependent dynamics remain limited. This study systematically investigates the hydraulic performance, cavitation characteristics, and dynamic pressure pulsations of a centrifugal fire pump under various flow conditions (50%–150% of the design flow rate) through combined numerical simulations and experiments. Steady simulations were conducted using the standard κ-ε turbulence model, while unsteady simulations were performed with a 2° angular time step to capture the transient interactions between the impeller and the volute as well as the resulting dynamic pressure pulsations. Key results revealed that: At low flow (60% Qd), Radial force amplitudes increased by 40%, accompanied by 9.86 Hz low-frequency pulsations attributed to backflow-induced instabilities; At high flow (150% Qd), The critical cavitation number σ₃% surged to 0.961, indicating a 2.6-fold cavitation risk compared to the design condition (σ₃% = 0.376); The findings provide actionable strategies for optimizing pump design and operational stability in firefighting systems.
No takes yet. Share an insight, caveat, or question.
Hao et al. (2025) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: