January 25, 2026IET Renewable Power Generation4 citationsOpen Access

Strengthening Renewable‐Rich Weak Grids Through Improved Voltage Stability and Fault‐Ride Through Capability

View Full Paper
SSSadnan SakibMZMuhammad Ahsan ZameeMHM. J. Hossain

Key Points

  • The aim is to enhance voltage stability and fault-ride through capability in weak transmission networks with high renewable energy integration.
  • Developed a cascaded control parameter optimization framework.
  • Introduced a novel dynamic resilience metric for optimization.
  • Utilized an enhanced particle swarm optimization algorithm for concurrent parameter optimization.
  • Validated on the Simplified 14 Generator Test System in Southeast Australia.
  • Voltage overshoot reduced from 25%–40% to 6%–25%.
  • Fault clearing times extended from 55–70 ms to 255–270 ms.
  • Validated against AEMC and IEEE standards, confirming compliance.

Abstract

ABSTRACT The large‐scale integration of renewable energy sources such as photovoltaic and wind farms presents significant challenges to voltage stability and fault‐ride through capability, particularly in weak transmission networks characterized by low inertia and high impedance. Advancing carbon neutrality and energy sustainability demands flexible and adaptive control strategies capable of supporting diverse renewable technologies. This research introduces a cascaded control parameter optimization framework to enhance system stability and resilience in scenarios with high renewable energy penetration. Central to this framework is developing a novel dynamic resilience metric, which guided the optimization process by minimizing transient, extending permissible fault‐clearing times, and strengthening post‐recovery. An enhanced particle swarm optimization algorithm is employed to concurrently optimize parameters across plant models, electrical systems, and generator controllers, all in alignment with the PJM model development guidelines. This framework is validated on the Simplified 14 Generator Test System (Area 5), representative of Southeast Australia's grid, and verified for compliance with AEMC fault‐clearing requirements and IEEE 1947‐2003 standard. Case studies demonstrate its effectiveness and adaptability, with voltage overshoot reduced from 25%–40% to 6%–25%, and fault clearing times extended from 55–70 ms to 255–270 ms. These results confirm that the proposed approach offers a robust solution for integrating renewables into weak grids, enhancing reliability and supporting the shift toward a sustainable energy future.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Sakib et al. (2026) studied this question.

synapsesocial.com/papers/6975b2eafeba4585c2d6e709https://doi.org/10.1049/rpg2.70188