Buildings are not airtight, leading to air infiltration, defined as the uncontrolled flow of outdoor air into indoor spaces. These airflows have a detrimental impact on energy demand and consumption, making their accurate estimation in building energy performance assessment tools essential. In Spain, the current tools allow the use of four infiltration models: N-factor, LBL, AIM-2, and EN 16798–7. This study compares these four approaches using TRNSYS energy simulations applied to a real single-family dwelling. The building envelope was characterized by performing a Blower Door Test, and the analysis was extended to eight cities with different climatic conditions. The maximum difference in the estimated energy impact among the models ranged from 6.1% to 12.2%. In climates with mild winters and higher wind intensity, the differences between models were less pronounced, ranging from 1.29 to 2.57 kWh/m 2 ·year. Conversely, in colder climates with lower wind intensity, the differences were substantially higher, ranging from 2.8 to 7.37 kWh/m 2 ·year. These results highlight the importance of selecting an appropriate infiltration model based on climatic conditions. For colder climates with low wind intensity, the AIM-2 and EN 16798–7 models are recommended.