Study of a harmonic current compensation system using a hysteresis-controlled active filter: Design, sizing and optimization

View Full Paper
CNChristian Vunda NgulumingiNBNarcisse Meni BabakidiJMJordan Kondatata Mbambu

Key Points

  • This research aims to design, size, and optimize a hysteresis-controlled active filter for harmonic current compensation.
  • Conducted experimental measurements in an industrial setting.
  • Utilized analytical sizing methodology and parametric calculations.
  • Implemented rigorous optimization strategies for effective design.
  • Measured total harmonic distortion current (THDi) at 43.95%.
  • Identified dominant harmonics at rank 5 (38%) and rank 7 (16%).
  • Demonstrated successful implementation in an industrial complex.

Abstract

This article presents a comprehensive study on the design, sizing, and optimization of a parallel active filter (FAT1) using a hysteresis control strategy for harmonic current compensation in an industrial environment. The study, conducted at the BRALIMA/Kinshasa industrial complex, is based on experimental measurements revealing a THDi of 43.95% with a dominance of harmonics of rank 5 (38%) and 7 (16%). The article details the analytical sizing methodology, rigorous parametric calculations, and technical compromises necessary for the industrial implementation of the system.