Model shows increased marginal curtailment in GB's future electricity market, suggesting implications for planning.
High Variable Renewable Electricity (VRE) penetration inevitably causes curtailment (shedding), normally measured by average curtailment. Marginal curtailment (mc, the fraction of potential output curtailed by the last MW) can be many times higher, raising the long-run marginal cost of investment, proportional to 1/(1-mc). A unit commitment and efficient dispatch model of Britain divided into seven zones by transmission constraints in 2030 demonstrates that these constraints considerably increase mc compared to no congestion despite the considerable expansion of transmission, interconnectors and storage that mitigate curtailment. Current auction design favours levelised costs ignoring curtailment, but long-run marginal costs may be 90% higher, arguing for careful locational planning.
No takes yet. Share an insight, caveat, or question.
Chyong et al. (2025) studied this question.