Investigates sensor effects on voltage regulation and congestion management, indicating optimum smart grid operations.
This study investigates the impact of monitoring infrastructure characteristics (specifically sensor penetration and measurement accuracy) on the effectiveness of voltage regulation and congestion management within distribution networks. As distribution system operators transition toward active management, the integration of Distributed renewable Generation (DG) and demand response introduces significant physical and cyber-physical uncertainties. To address these challenges, a smart grid service framework has been employed to optimize flexibility resources from aggregated users and DG inverters through a genetic algorithm. The framework was tested on the IEEE European Low Voltage Test Feeder across various scenarios defined by distributed monitoring systems’ penetration and their measurement accuracy. Results show that sensor penetration has a dominant impact: increasing monitoring coverage from 0% to 100% raises the percentage of cases with fewer than one residual congestion from 46.2% to 91.9% (sensors with an accuracy class of 2%), reaching 97.9% with an accuracy class of 0.5%, while voltage violations are eliminated under full monitoring. These findings suggest that widespread sensor deployment, with a suitable measurement accuracy, is a fundamental prerequisite for reliable and efficient smart grid operation.
No takes yet. Share an insight, caveat, or question.
Carere et al. (2026) studied this question.