Demonstrates improved voltage sag detection in industrial settings, suggesting enhanced power quality monitoring capabilities.
Voltage sags pose severe risks to sensitive equipment in modern industries, requiring power quality monitoring equipment to possess fast and accurate sag detection capabilities. The traditional second-order generalized integrator (SOGI) will have oscillation phenomena in the case of DC offset, low-frequency harmonics, and high-frequency impulse noise. This study introduces a strong detection algorithm that combines Adaptive Composite Morphological Filtering (ACMF) with an improved Mixed Second- and Third-Order Generalized Integrator (MSTOGI). First, the ACMF pre-filtering module dynamically adjusts the scale of composite structuring elements through periodic parameter optimization, effectively filtering high-frequency random impulses while preserving the sharp transitions of abrupt voltage changes. Second, MSTOGI eliminates DC offset, and optimizes the gain coefficient to achieve the best dynamic response speed. Ultimately, a cascaded notch filter (CNF) module focuses on and removes even-order harmonic ripples caused by the synchronous reference frame transformation. Simulation results indicate that under severe grid conditions involving multiple composite distortions, the proposed architecture reduces the sag detection time to within 1.0 ms under typical operating conditions, with steady-state phase errors strictly controlled within a ±2° range. This method provides a reliable solution for DVR and UPS.
No takes yet. Share an insight, caveat, or question.
Zhou et al. (2026) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: