PulseExploreJournal ClubDebatesTrendingResearchersJournals
Instagram
HomeExploreJournal ClubTrending
Synapse
⌘+K
Synapse
April 23, 2026Energy Conversion and Economics2 citationsOpen Access

Stability analysis of parallel virtual synchronous generators and suppression of low‐frequency oscillations

View Full Paper
PZPeng ZhangShenyang University of TechnologyHWHaixin WangShenyang University of TechnologyMXMingchao XiaShenyang University of Technology

Key Points

  • The aim is to analyze stability and control oscillations in multi-parallel virtual synchronous generators in power systems.
  • Establishing a small-signal model for multi-VSG parallel connection.
  • Constructing a Phillips-Heffron model for identifying oscillation causes.
  • Developing and validating a virtual power system stabilizer control strategy through MATLAB/Simulink simulations.
  • The proposed control strategy significantly suppresses low-frequency oscillations.
  • Enhanced system stability compared to conventional control methods.

Abstract

Abstract With the increasing penetration of power electronic devices in power systems, virtual synchronous generator (VSG) technology has garnered widespread attention for its ability to provide inertia and damping support to the grid. However, while simulating the external characteristics of synchronous generators, this technology also introduces inherent rotor oscillation issues. Particularly in multi‐machine parallel operation, insufficient system damping can easily lead to low‐frequency oscillations, threatening system stability and equipment safety. To address this issue, this paper first establishes a small‐signal model for multi‐VSG parallel grid connection. Subsequently, a Phillips‐Heffron model tailored for multi‐VSG parallel structures is constructed, revealing the fundamental cause of system oscillations under disturbances. Building upon this foundation and drawing inspiration from traditional power system stabilizer design principles, a virtual power system stabilizer control strategy tailored for multi‐VSG parallel grid‐connected systems is proposed. Finally, the proposed control strategy is validated through MATLAB/Simulink simulations. The simulation results demonstrate that, compared to conventional control methods, the proposed VPSS control strategy effectively suppresses low‐frequency oscillations in the system, significantly enhancing overall stability.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Zhang et al. (2026) studied this question.

synapsesocial.com/papers/69e9baa885696592c86ecbc1https://doi.org/10.1049/enc2.70036
Ask AI
Helpful
Bookmark
Share
View Full Paper

Also Consider

Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context:

  1. 1Inter-Area Oscillation Analysis of Power System Integrated With Virtual Synchronous Generators2024 · 30 citations
  2. 2An Additional Damping Torque Method for Low-Frequency Stability Enhancement of Virtual Synchronous Generators2024 · 43 citations
  3. 3An Improved Damping Method for Virtual Synchronous Machines2019 · 149 citations
  4. 4Analysis and Suppression Strategy of Synchronous Frequency Resonance for Grid-Connected Converters With Power-Synchronous Control Method2023 · 42 citations
  5. 5Cooperative Adaptive Control of Multi-Parameter Based on Dual-Parallel Virtual Synchronous Generators System2023 · 44 citations