In distribution networks, traditional fault location methods have insufficient anti-interference capability and low accuracy in locating high-resistance grounding faults. To address these issues, a distribution network fault location method on the basis of SimAM-GraphSAGE-GAT is proposed. Firstly, the distribution network topology structure is converted into an adjacency matrix, and the electrical parameters of the faulty line are incorporated as node features into the graph structure of the network. Subsequently, the sampling and aggregation mechanism of GraphSAGE is used for learning node representation. Features are refined using SimAM. As a parameter-free attention mechanism, SimAM improves the ability of the model to capture important fault information. Then, the multi-head attention mechanism of GAT is introduced to enhance the representation of neighborhood relationships. Finally, GraphSAGE is utilized once again for deep aggregation, with a view to localizing faults by node classification. An IEEE 33-node distribution network model is adopted to verify the effectiveness of the algorithm in the experiment. The results show that this method can maintain high positioning accuracy even under the tested conditions, such as high-resistance grounding, noise interference, and data loss.
Bao et al. (Mon,) studied this question.