With the increasing penetration of renewable energy generation, large-scale voltage dips may cause significant active power deficits and threaten system frequency stability. To address the issue, this article proposes a two-stage control strategy to enhance the frequency support capability of renewable energy plants by maximizing converter utilization during asymmetric grid voltage dips. First, a qualitative analysis of converter active power capacity considering current capacity constraints under grid faults is conducted to establish the basis for mitigating system-wide active power deficits. Second, individual phase current constraints are formulated for converters under asymmetric voltage conditions to achieve full utilization of converter capacity. Based on this, a two-stage control strategy for renewable energy plants is proposed, where plant-level convex optimization models for both pre-fault and post-fault conditions are established. By optimally allocating current references of converters within the plants, the requirement of grid codes is satisfied, and the overall frequency support capability of plants is effectively improved. Simulation results demonstrate that the proposed strategy raises the system frequency nadir from 49.58 Hz to 49.66 Hz under a minor fault and from 49.06 Hz to 49.11 Hz under a severe fault, confirming its effectiveness in enhancing the frequency support capability of renewable energy plants.