Instabilities related to dc-side resonances can occur in voltage-source-converter-based high voltage dc (VSC-HVDC) when resonances originated in dc-transmission links coincide with a nonpassive behavior of one of the VSCs within the VSC-HVDC system. Through Nyquist stability criterion, it is shown in this paper that when the VSC that controls the direct voltage has a nonpassive behavior, the size of dc-side resonance peak also has a negative impact on the instability, i.e., the higher the resonance peak, the greater the risk of instability. Then, the impact of transmission link configurations on the dc-side resonance characteristic is investigated, including overhead transmission lines and dc-side filters. Based on the analysis presented in this paper, it is proposed that, around the dc-side resonance frequency, the magnitude of the VSC subsystem transfer function should be limited to the inverse of the resonance peak at highest. Finally, time-domain simulations show the effectiveness of the proposed countermeasure in stabilizing the system.
No takes yet. Share an insight, caveat, or question.
Pinares et al. (2016) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: